消防排煙風(fēng)機空間排煙量最基本要求
The most basic requirements of smoke exhaust volume in the space of fire smoke exhaust fan.

消防排煙風(fēng)機是高層建筑排煙通風(fēng)的重要設(shè)備,發(fā)揮著非常大的作用。隨著應(yīng)用的增多市場上也出現(xiàn)了各種型號的風(fēng)機,但是由于消防排煙風(fēng)機的特殊作用,其性能要求是相同的,消防排煙風(fēng)機的空間排煙量需要滿足以下要求,才能夠發(fā)揮其高效作用。
Fire smoke exhaust fan is an important equipment of smoke exhaust and ventilation in high-rise buildings, which plays a very important role. With the increase of application, there are various types of fans in the market. However, due to the special role of fire smoke exhaust fan, its performance requirements are the same. The space smoke exhaust volume of fire smoke exhaust fan needs to meet the following requirements to play its efficient role.

ISO認證

一個防煙分區(qū)排煙或凈空高度大于6.0m的不劃防煙分區(qū)的房間時,應(yīng)按每平方米面積不少于60m3/h計算(單臺風(fēng)機最小排煙量應(yīng)不少于7200m3/h)。
For a smoke control zone or a room without smoke control zone whose clearance height is greater than 6.0m, the calculation shall be based on an area of not less than 60m3 / h per square meter (the minimum smoke exhaust volume of a single fan shall not be less than 7200m3 / h).

兩個或兩個以上防煙分區(qū)排煙時,應(yīng)按最大防煙分區(qū)面積每平方米不少于120m3/h計算。中庭體積少于17000時,其排煙量按其體積的6次/h換氣計算;中庭體積大于17000時,其排煙量按其體積的4次/h換氣計算;但最小排煙量不應(yīng)小于102000m3/h。
When smoke is discharged from two or more smoke control zones, the maximum smoke control zone area per square meter shall not be less than 120m3 / h. When the volume of atrium is less than 17000, the smoke exhaust volume shall be calculated as per 6 times / h of its volume; when the volume of atrium is greater than 17000, the smoke exhaust volume shall be calculated as per 4 times / h of its volume; however, the minimum smoke exhaust volume shall not be less than 102000m3 / h.

工廠實景

高層建筑防煙樓梯間及其前室、消防電梯間前室或合用前室,當(dāng)裙房以上部位利用可開啟外窗進行自然排煙,裙房部分不具備自然排煙條件時,其前室或合用前室應(yīng)設(shè)置局部機械排煙設(shè)施,其排煙量按前室每平方米不少于60m3/h計算。
In the smoke-proof staircase and its front room, the front room of fire elevator room or shared front room of high-rise building, when the part above the podium uses the openable external window for natural smoke exhaust, and the part of the podium does not have the conditions for natural smoke exhaust, the front room or shared front room shall be equipped with local mechanical smoke exhaust facilities, and the smoke emission shall be calculated as per the front room of not less than 60m3 / h per square meter.

以上就是目前消防排煙風(fēng)機應(yīng)用比較多的領(lǐng)域的排煙量基本要求,只有滿足以上要求,消防排煙風(fēng)機才能算是合格的設(shè)備,才能夠發(fā)揮其自身的性能優(yōu)勢。
The above is the basic requirements of smoke exhaust volume in the field of fire smoke exhaust fan application. Only if the above requirements are met, the fire smoke exhaust fan can be regarded as qualified equipment, and can play its own performance advantages.

CCC證書

果我哋喺應(yīng)用過程中發(fā)現(xiàn)救火排煙風(fēng)機嘅流量過大,唔符合使用要求或者系短時間內(nèi)要較小嘅流量,我哋可以利用節(jié)流裝置進行較。喺救火排煙風(fēng)機嘅車、泊車或者運轉(zhuǎn)過程中,如發(fā)現(xiàn)唔正?,F(xiàn)象時,應(yīng)即刻進行檢查。對寒暑表同油標(biāo)嘅靈敏性定期檢查,并且應(yīng)該控制軸承箱油位喺規(guī)定嘅允許裏面食.次次拆修后救火排煙風(fēng)機應(yīng)更換機油之外,重應(yīng)定期更換機油。對E式傳動嘅軸承座應(yīng)定期(季度)檢查,清洗同補加機油,以防軸承燒壞。